* THE FOLLOWING ARE MINIMUM SPECIFICATIONS UNLESS SPECIFIED BY OTHERS *

SOIL BEARING CAPACITY STEMCO BASEPLATE SIZE (minimum) FOOTING CAPACITY
(unfactored)
FOOTING CAPACITY
(unfactored)
DIMENSION DIMENSION AMOUNT OF REBAR & SIZE REBAR SPACING IN EACH DIRECTION
psf (inches) (lbs) (KN) S (inches) H (inches) (inches)
2000 4 x 6 16000 71 35 10 5-10M 7.5
4 x 8 20000 89 39 10 6-10M 7
4 x 8 25000 111 44 10 6-10M 8
4 x 8 30000 133 48 10 7-10M 7.5
4 x 8 35000 156 52 10 7-10M 8
6 x 6 40000 178 56 11 8-10M 7.5
6 x 6 50000 222 63 12 10-10M 6.5
6 x 6 60000 267 69 13 12-10M 6
6 x 6 70000 311 74 13 14-10M 5.5
3000 4 x 6 16000 71 28 10 4-10M 8
4 x 8 20000 89 32 10 5-10M 7
4 x 8 25000 111 35 10 5-10M 7.5
4 x 8 30000 133 39 10 5-10M 8.5
4 x 8 35000 156 42 10 6-10M 7.5
6 x 6 40000 178 45 11 7-10M 7
6 x 6 50000 222 50 12 8-10M 6.5
6 x 6 60000 267 55 13 10-10M 5.5
6 x 6 70000 311 60 13 10-10M 6


Column Assembly Sketch FOOTING NOTES:

  1. Concrete strength shall be a minimum of 20 Mpa (3000 psi) at 28 days.
  2. Concrete shall be Type 10 or Type 50 with a max 20 mm (3/4") aggregate and 3" slump.
  3. Rebar shall be grade 400.
  4. Rebar is to be tied at all intersections.
  5. Column shall be placed in the center of the footing. Eccentric loading reduces the footing capacity.
STEMCO Column Assembly
  1. Support and brace the beam in its intended postion using lumber.
  2. Measure the distance from the top of footing to the underside of the beam and write down this number.
  3. IMPORTANT Position the threaded rod in the support head at the midpoint of its extension to allow for future up or down adjustment.
  4. Measure the length of your original column from the bottom of the baseplate to the top of the head/top plate assembly.
  5. Subtract Step 2 and Step 4 measurements and record number.
  6. Remove head and trim top of column by the value calculated in Step 5 using an approved metal cutting blade. The cut must be level, true and free of nicks or burrs.
  7. Centre the assembled column under the beam and centre on the footing. Plumb column in both directions.
  8. Drill 3/16" x 2.5" holes into the wood beam through holes in the top plate and install 1/4" x 3" lag bolts.
  9. Column bases shall be encased by a floor slab or equivalently secured as specified by others.
NOTE: As required by C.S.A. 086, and TrusJoist, all beams shall have adequate attachment and positioning of lateral bracing to achieve member stability (as determined by the building designer).